Armored instrumentation cable

Copper cable, PVC insulation 105°C, twisted in pairs, triples, or quadruples, individual shielding with aluminum-polyester tape with tinned copper drain conductor, galvanized iron wire armor with tying counter-spiral, PVC Hydrocarbons sheath. The cable does not propagate fire, resists hydrocarbons and sunlight. Design voltage 300V. Maximum 150 V and 5A according to NEC article 727. Service voltage 50 V in AEA 90364. Suitable for MBTF, MBTS.

For use in these industries

Infrastructure and Transportation

Oil & Gas

Mining

Power Generation

Properties

Oil Resistance

Sun Resistance

Water Resistance

Fire Resistance

Cold Resistance

Technical assessments

Normas de construcción y ensayos del cable para potencia limitada: UL13, ASTM B8

Normas de construcción y ensayos del cable para instrumentación: IEC 60092-376, IEC 60228

Ensayo de no propagación del incendio IEC 60332-3-24 categoría A

Ensayo de emisión de gases toxico: IEC 60754-1 menor a 15%

Ensayo de envejecimiento en Aceite Nr. 2 a 100°C, 70 hs

Ensayo de envejecimiento en Fuel Oíl a 70°C, 168 hs

Ensayo de envejecimiento en cámara UV, 1000 hs

Cumple UIC 895 OR, Variación de la resistencia a la tracción 30%, variación del alargamiento a la rotura 40%

Datahseets

Carácteristicas Constructivas

Características Eléctricas

Colores de la aislación y envoltura

Colores de la aislación y envoltura para alarma de incendio

Colores de la aislación y envoltura para seguridad intrínseca

Applicacations

AEA 90079

EXPLOSIVE ATMOSPHERES Classification of Areas Explosive Atmospheres IEC 60079

AEA 95101

Regulation of underground external energy and telecommunications lines

IEC 60364

Regulations for the execution of electrical installations in buildings


Engineered to Meet Quality Standards

Quality You Can Trust

Instituto Argentino de Normalización y Certificación

Asociación Electrotécnica Argentina

International Electrotechnical Commission